Ferrule
FWC 600V 6-32A
Electrical Characteristics | Ordering Information | Dimensions | ||||||
---|---|---|---|---|---|---|---|---|
Size | Rated Current RMS-Amps | I2t (A2 S) | Watts Loss | Part Number | Carton Qty. | Carton Weight (kg) | Figure Number | |
Pre-Arc | Clearing At 660V | |||||||
10x38 mm | 6 | 4 | 30 | 1.5 | FWC-6A10F | 10 | 0.100 | Fig. 1 |
10x38 mm | 8 | 6 | 50 | 2.0 | FWC-8A10F | 10 | 0.100 | Fig. 1 |
10x38 mm | 10 | 9 | 70 | 2.5 | FWC-10A10F | 10 | 0.100 | Fig. 1 |
10x38 mm | 12 | 15 | 120 | 3.0 | FWC-12A10F | 10 | 0.100 | Fig. 1 |
10x38 mm | 16 | 25 | 150 | 3.5 | FWC-16A10F | 10 | 0.100 | Fig. 1 |
10x38 mm | 20 | 34 | 260 | 4.8 | FWC-20A10F | 10 | 0.100 | Fig. 1 |
10x38 mm | 25 | 60 | 390 | 6.0 | FWC-25A10F | 10 | 0.100 | Fig. 1 |
10x38 mm | 32 | 95 | 600 | 7.5 | FWC-32A10F | 10 | 0.100 | Fig. 1 |
1 kg = 2.2 lbs. 1 lb = 0.45 kg
• Interrupting rating 200kA RMS Symmetrical. 1 kg = 2.2 lbs. 1 lb = 0.45 kg
• Watts loss provided at rated current.
• (400 Vdc/Interrupting rating 50kA) U.L. Recognition: 32A
• (700 Vdc/Interrupting rating 50kA) U.L. Recognition: 6 - 25A
Dimensions
Fig. 1: 6-32 Amp Range
Electrical Characteristics
Total Clearing I2t
The total clearing I2t at rated voltage and
at power factor of 15% are given in the
electrical characteristics. For other volt-
ages,the clearing I2t is found by multi-
plying by correction factor, K, given as
a function of applied working voltage,
Eg, (RMS).
|
Arc Voltage
This curve gives the peak arc voltage,
UL, which may appear across the fuse
during its operation as a function of the
applied working voltage, Eg, (RMS) at a
power factor of 15%.
|
Power Losses
Watts loss at rated current is given in
the electrical characteristics. The curve
allows the calculation of the power
losses at load currents lower than the
rated current . The correction factor, Kp,
is given as a function of the RMS load
current, Ib, in % of the rated current .
|