FWC FUSE

Home » Our Products » Fuses » Low Voltage » FWC FUSE

Ferrule
FWC 600V 6-32A

Electrical CharacteristicsOrdering InformationDimensions
SizeRated Current RMS-AmpsI2t (A2 S)Watts LossPart NumberCarton Qty.Carton Weight (kg)Figure Number
Pre-ArcClearing At 660V
10x38 mm 6 4 30 1.5 FWC-6A10F 10 0.100 Fig. 1
10x38 mm 8 6 50 2.0 FWC-8A10F 10 0.100 Fig. 1
10x38 mm 10 9 70 2.5 FWC-10A10F 10 0.100 Fig. 1
10x38 mm 12 15 120 3.0 FWC-12A10F 10 0.100 Fig. 1
10x38 mm 16 25 150 3.5 FWC-16A10F 10 0.100 Fig. 1
10x38 mm 20 34 260 4.8 FWC-20A10F 10 0.100 Fig. 1
10x38 mm 25 60 390 6.0 FWC-25A10F 10 0.100 Fig. 1
10x38 mm 32 95 600 7.5 FWC-32A10F 10 0.100 Fig. 1
1 kg = 2.2 lbs.    1 lb = 0.45 kg
• Interrupting rating 200kA RMS Symmetrical. 1 kg = 2.2 lbs.    1 lb = 0.45 kg
• Watts loss provided at rated current.
• (400 Vdc/Interrupting rating 50kA) U.L. Recognition: 32A
• (700 Vdc/Interrupting rating 50kA) U.L. Recognition: 6 - 25A

Dimensions
Fig. 1: 6-32 Amp Range


Electrical Characteristics

Total Clearing I2t
The total clearing I2t at rated voltage and
at power factor of 15% are given in the
electrical characteristics. For other volt-
ages,the clearing I2t is found by multi-
plying by correction factor, K, given as
a function of applied working voltage,
Eg, (RMS).
Arc Voltage
This curve gives the peak arc voltage,
UL, which may appear across the fuse
during its operation as a function of the
applied working voltage, Eg, (RMS) at a
power factor of 15%.

 
Power Losses
Watts loss at rated current is given in
the electrical characteristics. The curve
allows the calculation of the power
losses at load currents lower than the
rated current . The correction factor, Kp,
is given as a function of the RMS load
current, Ib, in % of the rated current .