Application
For power and control cable use in machineries,tools,production lines,conveyor belts and other electrical installations.Suitable for installations on fixed and flexible application with medium mechanical stress without tensile stress or forced movements.
Construction
Stranded bare copper conductor according to IEC 60228, class 5
Polyethylene (PE) Core insulation
Core indentification : colour coded according to HD-308
Cores are twisted in layers
PVC inner sheath
Tinned cooper wire braided screening,coverage approx.85% over alluminium foil tape (double screened)
PVC outer sheath,UV resistant,colour : black
Electrical & Technical Data
Working voltage Uo/U | : 600/1000 V |
Test Voltage | : 3500 VAC/5 min |
Insulation Resistance | : 20 MΩ x km |
Working temperature | : -50C to + 700C (Moved) |
: -300C to + 700C (Fixed) | |
Minimum bending radius | : 15 x cable diameter |
Cross section | Current Carrying | Capacitance Cond./Cond. | Capacitance Cond./Shield. | Outer Diameter Approx | Cable Weight Approx | ||
---|---|---|---|---|---|---|---|
(mm2) | Capacity (A) | (ca.nF/km) | (ca.nF/km) | (mm) | (Kg/Km) | ||
4 x 1.5 | 18 | 70 | 110 | 14.1 | 297 | ||
4 x 2.5 | 26 | 80 | 130 | 15.1 | 361 | ||
4 x 4 | 34 | 90 | 150 | 16.6 | 460 | ||
4 x 6 | 44 | 110 | 170 | 18.0 | 572 | ||
4 x 10 | 61 | 120 | 190 | 20.5 | 809 | ||
4 x 16 | 82 | 130 | 220 | 23.4 | 1150 | ||
4 x 25 | 125 | 145 | 230 | 27.6 | 1657 | ||
4 x 35 | 155 | 150 | 260 | 31.1 | 2185 | ||
4 x 50 | 190 | 175 | 290 | 36.4 | 3062 | ||
4 x 70 | 245 | 180 | 300 | 41.4 | 4080 | ||
4 x 95 | 300 | 195 | 320 | 46.6 | 5344 | ||
4 x 120 | 345 | 215 | 340 | 51.3 | 6599 | ||
4 x 150 | 400 | 230 | 360 | 57.3 | 8207 | ||
4 x 185 | 455 | 240 | 380 | 63.2 | 10068 | ||
4 x 240 | 540 | 250 | 410 | 68.9 | 12180 | ||
*Above given admissible current carrying correspond to an ambient temperature of 300C.For higher temperatures the following correction factors apply.
temperature 0C | 35 | 40 | 45 | 50 | 55 |
factor | 0.94 | 0.87 | 0.79 | 0.71 | 0.61 |