FRC 1000
Construction
Conductor | : Stranded plain annealed copper wire to IEC-60228 class 2 |
Flame barrier | : Glass mica tape |
Insulation | : XLPE compound |
Sheath | : Low Smoke Zero Halogen compound, orange colour |
Technical Data
Voltage rating | : 600/1000V |
Test voltage | : 3500VAC/5 mins |
Operating temp. | : -400C to 900C |
Min. bending radius | : 8 x overall diameter of cable |
Product performance
Fire resistant test | : IEC - 60331; BS-6387 categories C,W & Z |
Flame propagation | : IEC - 60332-1; IEC-60332-3 categories A,B,C |
Oxygen density test | : ASTM D2863 min. 34% |
Smoke density test | : IEC-61034-1&2 |
Halogen content test | : IEC-60754-1 |
Acid gas emission | : IEC-60754-2 |
Data Sheet
Cores | Nominal area of conductor | Thickness of insulation | Thickness of sheaths | Approx. diameter overall | Approx. Weight |
---|---|---|---|---|---|
(mm2) | (mm) | (mm) | (mm) | (kg/km) | |
1 x | 1.5 | 0.7 | 1.4 | 6.4 | 55 |
1 x | 2.5 | 0.7 | 1.4 | 6.8 | 70 |
1 x | 4 | 0.7 | 1.4 | 7.4 | 90 |
1 x | 6 | 0.7 | 1.4 | 7.9 | 110 |
1 x | 10 | 0.7 | 1.4 | 8.9 | 160 |
1 x | 16 | 0.7 | 1.4 | 9.9 | 220 |
1 x | 25 | 0.9 | 1.4 | 12.2 | 330 |
1 x | 35 | 0.9 | 1.4 | 13.5 | 430 |
1 x | 50 | 10 | 1.4 | 15.0 | 560 |
1 x | 70 | 1,1 | 1.4 | 17.0 | 770 |
1 x | 95 | 1,1 | 1.5 | 19.0 | 1040 |
1 x | 120 | 1.2 | 1.5 | 20.8 | 1290 |
1 x | 150 | 1.4 | 1.6 | 23.0 | 1580 |
1 x | 185 | 1.6 | 1.6 | 25.3 | 1950 |
1 x | 240 | 1.7 | 1.7 | 28.3 | 2530 |
1 x | 300 | 1.8 | 1.8 | 31.0 | 3140 |
1 x | 400 | 2.0 | 1.9 | 34.7 | 3970 |
1 x | 500 | 2.2 | 2.0 | 38.5 | 4970 |
1 x | 630 | 2.4 | 2.2 | 43.5 | 6400 |