FRC 500
Construction
| Conductor | : Stranded plain annealed copper wire to IEC-60228 class 2 |
| Flame barrier | : Glass mica tape |
| Insulation | : XLPE compound |
| Sheath | : Low Smoke Zero Halogen compound, orange colour |
Technical Data
| Voltage rating | : 300/500V |
| Test voltage | : 2000VAC / 5 mins |
| Operating temp. | : -400C to 900C |
| Min. bending radius | : 8 x overall diameter of cable |
Product performance
| Fire resistant test | : IEC - 60331 ; BS-6387 categories C,W & Z |
| Flame propagation | : IEC-6332-1 ; IEC-60332-3 categories A,B,C |
| Oxygen density test | : ASTM D2863 min. 34% |
| Smoke density test | : IEC-61034-1&2 |
| Halogen content test | : IEC-60754-1 |
| Acid gas emission | : IEC-60754-2 |
Data Sheet
Cores | Nominal area of conductor | No. & diameter of wires | Thickness of insulation | Thickness of sheaths | Approx. diameter overall | Approx. Weight |
|---|---|---|---|---|---|---|
| (mm2) | (No./mm) | (mm) | (mm) | (mm) | (kg/km) | |
| 2 x | 1.5 | 7/0.53 | 0.5 | 1.0 | 9.1 | 105 |
| 2 x | 2.5 | 7/0.67 | 0.5 | 1.1 | 10.1 | 138 |
| 2 x | 4 | 7/0.85 | 0.6 | 1.1 | 11.7 | 197 |
| 3 x | 1.5 | 7/0.53 | 0.5 | 1.0 | 9.7 | 123 |
| 3 x | 2.5 | 7/0.67 | 0.5 | 1.1 | 10.8 | 167 |
| 3 x | 4 | 7/0.85 | 0.6 | 1.1 | 12.4 | 240 |
| 4 x | 1.5 | 7/0.53 | 0.5 | 1.1 | 10.7 | 153 |
| 4 x | 2.5 | 7/0.67 | 0.5 | 1.2 | 11.9 | 209 |
| 4 x | 4 | 7/0.85 | 0.6 | 1.2 | 13.9 | 302 |
| 5 x | 1.5 | 7/0.53 | 0.5 | 1.1 | 11.8 | 186 |
| 5 x | 2.5 | 7/0.67 | 0.5 | 1.2 | 12.1 | 255 |
| 7 x | 1.5 | 7/0.53 | 0.5 | 1.1 | 13 | 232 |
| 7 x | 2.5 | 7/0.67 | 0.5 | 1.2 | 14.4 | 322 |
| 10 x | 1.5 | 7/0.53 | 0.5 | 1.3 | 17 | 340 |
| 10 x | 2.5 | 7/0.67 | 0.5 | 1.3 | 18.9 | 470 |
| 12 x | 1.5 | 7/0.53 | 0.5 | 1.3 | 17.6 | 377 |
| 12 x | 2.5 | 7/0.67 | 0.5 | 1.4 | 19.6 | 527 |
| 19 x | 1.5 | 7/0.53 | 0.5 | 1.4 | 20.9 | 587 |
| 19 x | 2.5 | 7/0.67 | 0.5 | 1.5 | 23.3 | 823 |
| 24 x | 1.5 | 7/0.53 | 0.5 | 1.6 | 24.7 | 740 |
| 24 x | 2.5 | 7/0.67 | 0.5 | 1.7 | 27.6 | 1040 |